First off thanks for all the concerns. So far 2 resets in 3 or 4 months does have me knowing something is not right,but hardly enough to panic I'd think?
So far I pulled the panel cover off,checked tightness off ALL connections. Main was not loose but several other small circuits were VERY loose. Hooked amprobe over one leg and with dryer,stove,and water heater going plus lights etc. didn't get quite up to 60 amps. Voltage checked without loads 248 across both breaker terminals and 122 from each half to neutral. Now as I type this I bet I should of tested it with the loads going too.
Next trip to town going to pick up a spare breaker. Will change it out next time it trips or next power outage whichever comes first.
So far I pulled the panel cover off,checked tightness off ALL connections. Main was not loose but several other small circuits were VERY loose. Hooked amprobe over one leg and with dryer,stove,and water heater going plus lights etc. didn't get quite up to 60 amps. Voltage checked without loads 248 across both breaker terminals and 122 from each half to neutral. Now as I type this I bet I should of tested it with the loads going too.
Next trip to town going to pick up a spare breaker. Will change it out next time it trips or next power outage whichever comes first.