e said: (quoted from post at 13:21:59 12/03/09) To give you guys some background, I'm upgrading the electrical service on our farm to 400 amp. The current system comes in to a central pole, then branches out to each building. The new system will be underground and will come into the shop. From the shop, I will be running from one main panel to the barn, house, etc.
What I'm trying to determine is if I should have grounding rods for each building, or, should I run two hots, a nuetral, and a ground from each building to the main panel. My plan has been to ground each building seperatly with two 5/8" 8' rods etc etc. It feels better to me to ground as close to the point of use as possible. The distance I need to run from the main panel to each building is about 150'.
Now my other question pertains to grounding the barn. Do I need to give any special consideration to grounding a building with livestock? Would it be better to run a ground back to the main panel to minimize the potential for stray voltage?
you ask, "Would it be better to run a ground back to the main panel to minimize the potential for stray voltage?"
You can do that. The NEC has several instances of info on this topic & one must take care not to mis-apply any one instance to the wrong situation......it can be confusing.
Keep this all important over-riding statement in mind when setting up your grounding scheme: "Never create a situation where neutral load current is allowed to flow in the safety ground conductor."
How does that apply to your question, you might ask?
IF you choose to run both a safety ground & a neutral to your livestock barn, then to avoid having neutral load currents flowing in your safety ground, the two 'grounds' (neutral & safety) MUST be separated at the barn. Note, since they are common at the service entrance panel, if they were to be tied together (common) at the barn, now the neutral conductor and the safety ground conductors would simply be in parallel (essentially one conductor composed of 2 strands)...no good!
We sell tractor parts! We have the parts you need to repair your tractor - the right parts. Our low prices and years of research make us your best choice when you need parts. Shop Online Today. [ About Us ]
Today's Featured Article - A Brief History of Tractors in Australia - by Bob Kavanagh. After Captain Cook's exploration of the east coast in 1770 the British Government decided to establish a penal colony in Australia. The first fleet arrived in 1788 and consisted mainly of convicts who were poorly equipped and new little of farming techniques. The colony remained far from self-supporting and it was not until the early 1800's that things started to improve. Free settlers started to arrive, they followed the explorers across the mountains and where land was suitable set up farms. T
... [Read Article]
Latest Ad:
Sell 1958 Hi-Altitude Massey Fergerson tractor, original condition. three point hitch pto engine, Runs well, photos available upon request
[More Ads]
All Rights Reserved. Reproduction of any part of this website, including design and content, without written permission is strictly prohibited. Trade Marks and Trade Names contained and used in this Website are those of others, and are used in this Website in a descriptive sense to refer to the products of others. Use of this Web site constitutes acceptance of our User Agreement and Privacy Policy
TRADEMARK DISCLAIMER: Tradenames and Trademarks referred to within Yesterday's Tractor Co. products and within the Yesterday's Tractor Co. websites are the property of their respective trademark holders. None of these trademark holders are affiliated with Yesterday's Tractor Co., our products, or our website nor are we sponsored by them. John Deere and its logos are the registered trademarks of the John Deere Corporation. Agco, Agco Allis, White, Massey Ferguson and their logos are the registered trademarks of AGCO Corporation. Case, Case-IH, Farmall, International Harvester, New Holland and their logos are registered trademarks of CNH Global N.V.